Sign In | Join Free | My himfr.com
Home > Hall Effect Current Transducer >

Open Loop Type Hall Effect Current Transducer 500A Input 20mm Diameter

Nanjing Chieful Science & Technology Co., Ltd.
Contact Now
    Buy cheap Open Loop Type Hall Effect Current Transducer 500A Input 20mm Diameter from wholesalers
     
    Buy cheap Open Loop Type Hall Effect Current Transducer 500A Input 20mm Diameter from wholesalers
    • Buy cheap Open Loop Type Hall Effect Current Transducer 500A Input 20mm Diameter from wholesalers
    • Buy cheap Open Loop Type Hall Effect Current Transducer 500A Input 20mm Diameter from wholesalers

    Open Loop Type Hall Effect Current Transducer 500A Input 20mm Diameter

    Ask Lasest Price
    Brand Name : chieful
    Model Number : CS500E
    Certification : CE,Rohs,ISO9001
    Price : Negotiable
    Payment Terms : T/T
    Supply Ability : 100000pcs/month
    Delivery Time : 5 Days
    • Product Details
    • Company Profile

    Open Loop Type Hall Effect Current Transducer 500A Input 20mm Diameter

    500A , 20mm Diameter Hall Effect Current Transducer 4V output


    open loop device based on the measuring principle of the hall effect, with a galvanic isolation between primary and secondary circuit. It provides accurate electronic measurement of DC, AC or pulsed currents.


    Hall current sensors are widely applicable for acquisition and feeback control of current signals in the current monitoring,inverter,solar power management,current cabinet,DC motor drive and UPS servo control systems.

    Electrical characteristics
    TypeCS050ECS100ECS200ECS300ECS400ECS500E
    IPNPrimary nominal input current50100200300400500A
    IPMeasuring range of primary current0~±1000~±2000~±4000~±6000~±8000~±800A
    VOUTNominal output voltage4±1%V
    VCSupply voltage±12~±15(±5%)V
    ICCurrent consumptionVC=±15V <20mA
    VDInsulation voltageAC/50Hz/1min 2.5kV
    εLLinearity<1%FS
    VOOffset voltageTA=25℃ <±25mV
    VOMResidual voltageIPN→0 <±20mV
    VOTThermal drift of V0IP=0 TA=25~+85℃ <±1mV/℃
    TRResponse time≤3μs
    fFrequency bandwidth(-3dB)DC~20kHz
    TAAmbient operating temperature25~+85
    TSAmbient storage temperature40~+100
    RLLoad resistance≥10KΩ
    StandardQ/3201CHGL02-2016

    Dimensions of drawing (mm)

    Open Loop Type Hall Effect Current Transducer 500A Input 20mm Diameter

    Remarks

    ·Incorrect connection may lead to the damage of the sensor.
    ·VOUT is positive when the IP flows in the direction of the arrow.







    Quality Open Loop Type Hall Effect Current Transducer 500A Input 20mm Diameter for sale